SynthCool Stokes closed-loop adaptive liquid cooling control unit

Closed-loop adaptive coolant distribution unit (CDU)

SynthCool Stokes™ is a CDU series for high-density servers with cold-plate liquid cooling. It integrates heat exchange and coolant control in a standard cabinet footprint and modular design, with multiple configurations including L2L/L2A In-Rack and In-Row CDU solutions. This enables flexible deployment across a wide range of liquid cooling applications and power levels.

Download brochure
Application scenariosMedium-, large-, and hyperscale liquid-cooled data centers.

Stable liquid cooling circulation in different climates and room layouts.

Year-round free cooling

Higher secondary-side supply temperature makes better use of natural cooling sources for energy-saving operation across different climates.

Modular and flexible deployment

Supports side-by-side deployment with IT racks and online front/back maintenance to reduce operational complexity.

High reliability and redundancy

Integrates efficient heat exchanger, N+1 redundant circulation pumps, dual power supply, leak monitoring, and online maintenance for key parts.

Remote monitoring and cluster control

Key operating data is uploaded to the monitoring system for real-time visual management. Host information is automatically backed up during cluster control.

Technical specifications

Model

Model
Stokes™ CDU-L2A-0160
Frame size
2200×1200×1200mm
Rated heat exchange
160 kW

Secondary-side parameters

Pump
1+1 dual pumps
Coolant
Deionized water / EG25 / PG25
Rated supply/return temperature
45/55°C
Rated supply flow
14m³/h
Rated supply flow range
4~16m³/h
Available IT head
2.5bar
Supply/return pipe diameter
ISO 2in
Supply/return connection
Sanitary 2in clamp
System pressure rating
10bar
Make-up tank volume
18L
Filter precision
500 mesh

Primary-side parameters

Cooling medium
Air
Allowed air temperature
5-35°C
Rated air temperature
35°C
Rated air flow
34000m³/h
Maximum air flow
40000m³/h
Air filtration precision
20 mesh
Rated power consumption
12kW
Maintenance clearance
Front/back doors 1200mm wide as maintenance sides; front/back clearance not less than 1000mm

Power distribution system

Rated input voltage
380V-3PH-50HZ
Dual power support
Dual utility power supported, optional ATS

Environment system

Operating temperature
15~40°C
Operating relative humidity
8%~80%
Altitude
≤2000m
Storage temperature
-25~60°C
Storage relative humidity
5%~95%RH

You may also want to know

Progressive liquid cooling retrofit for existing data centers

Progressive liquid cooling retrofit for existing data centers

Based on Nusselt™ single-phase cold plates and Stokes™ rack-level CDU, SynthCool provides a low-cost, scalable retrofit path for existing data centers. It keeps the original architecture, supports phased deployment and hybrid air-liquid operation, and helps traditional facilities evolve smoothly toward liquid cooling.