芯寒智能
SynthCool Onsager single-phase immersion product

Single-phase immersion cooling series

SynthCool Onsager™ uses a modular CDU + TANK architecture. IT equipment is immersed directly in the TANK with the CDU deployed alongside it, offering a quieter, efficient, and deployable immersion retrofit path for medium- and low-density data centers.

Download brochure
Application scenariosMedium- and high-density immersion-cooled servers in small- to large-scale liquid-cooled data centers.

Modular immersion cooling system for existing data center retrofit.

Modular deployment

Cabinet-style CDU + TANK architecture supports flexible deployment and online maintenance, with a rated heat exchange capacity of 50 kW.

Redundant system design

Integrates plate heat exchanger, 1+1 redundant pumps, dual power supply and leak monitoring for maximum reliability.

Year-round free cooling

Higher secondary-side supply temperatures enable greater use of natural cooling sources, reducing cooling energy consumption.

Precise temperature control

Steady-state accuracy of ±0.5°C and dynamic response accuracy of ±2°C ensure stable supply temperatures control.

Technical specifications

Model

Model
Onsager™ 1PIC-50
Frame size
2100×600×900mm (CDU) 1350×1250×900mm (TANK)
Rated heat exchange
50 kW

CDU secondary-side parameters

Pump
1+1 dual pumps
Coolant
Fluorinated liquid / silicone oil
Rated supply/return temperature
35/45°C
Rated supply flow
11m³/h
Rated supply flow range
0~12m³/h
Available IT head
2.5bar
Supply/return pipe diameter
ISO 2-1/4in
Supply/return connection
Sanitary 2-1/4in clamp
System pressure rating
5bar
Filter precision
50μm

Power distribution system

Rated input voltage
380V-3PH-50HZ
Dual power support
Dual utility power supported, optional ATS

Primary-side parameters

Coolant
Softened water, supports up to 30% glycol solution
Allowed inlet temperature
15-31°C
Rated inlet/outlet temperature
32/37°C
Rated coolant flow
8.6m³/h (based on softened water)
Supported inlet flow range
0~10m³/h
Inlet/outlet pipe diameter
ISO 1-3/4“
Inlet/outlet connection
Sanitary 1-3/4“ clamp
System pressure rating
10bar
Filter precision
300μm
Rated power consumption
0.65kW (cold standby pump) / 0.55kW (hot standby pump)
Maintenance clearance
Front/back doors 600mm wide as maintenance sides; front/back clearance not less than 1000mm

Environment system

Operating temperature
15-40°C
Operating relative humidity
8%~80%
Altitude
≤2000m
Storage temperature
-25~60°C
Storage relative humidity
5%~95%RH

You may also want to know

Green immersion retrofit for medium- and low-density data centers

Energy-saving immersion retrofit for medium- and low-density data centers

Based on Onsager™ single-phase immersion and Stokes™ CDU, SynthCool provides an efficient immersion liquid-cooling upgrade for traditional CPU server clusters, enabling quiet operation, lower energy use, and greener data center retrofit without replacing hardware.

Learn more
Back to products