SynthCool Landau phase-change immersion product

Landau 2PIC Series

The SynthCool Landau 2PIC two-phase immersion cooling solution adopts a low-boiling-point dielectric fluid to fully immerse server electronic components, achieving 100% liquid cooling coverage. The refrigerant directly contacts heat-generating components and absorbs heat through boiling (phase change), ensuring stable, uniform cooling for ultra high-density servers.

Application scenariosFor GPU servers, AI computing clusters, supercomputing centers, and high-density data centers.

Product features

Full Immersion, Efficient Cooling

Refrigerant directly contacts heat sources to minimize thermal resistance. Harnessing latent heat delivers 100+ W/cm² cooling capacity for high heat-flux chips.

Space-Saving Deployment

Delivers a power density up to 200 kW per cabinet within 2240 × 600 × 1600 mm (H × W × D) space, maximizing compute capacity per unit of server room floor space.

Uniform Cooling, Stable Operation

Insulating fluid eliminates short-circuit risks, while full immersion reduces hot spots and thermal fluctuations for stable chip performance.

Fanless & Energy-Efficient

Liquid immersion removes component heat without server fans. Pairs with matched cooling sources for free cooling to lower total PUE.

Technical specifications

Specifications

Model
Landau 2PIC-400
Rated heat exchange
400 kW
Dimensions
Rack: 2200 × 600 × 1600 mm CDU: 2200 × 1200 × 1600 mm

Secondary-Side Specifications

Refrigerant
Opteon 2P50 / HFP-D
Pump
1+1 dual pumps / single pump (optional)

Primary-Side Specifications

Primary-side heat exchange
Water-cooled
Refrigerant
Softened water / PG25 / EG30
Inlet temperature
15–35°C
Rated inlet/outlet temperature
35/43°C
Connection type
DIN flange
System pressure rating
10 bar
Hydraulic requirement
1–1.5 bar
Filter type
Primary side, 300 mesh

General Specifications

HMI
7-inch local touchscreen display. Standard RS-485 communication interface, Modbus RTU protocol. Optional RJ45 Ethernet interface, Modbus TCP protocol.
Maintenance clearance
Front and rear clearance ≥ depth of unit

Two-Phase Immersion Cooling Computer Rack

Frame size
2240 × 600 × 1600 mm
Usable space
44OU / 44RU
Power input unit
The centralized power supply modules can be installed at the top or bottom of the rack. Supports up to four 54 V power supply enclosures, with a maximum power capacity of 432 kW. The 24 PSUs support N+1/N+X redundancy.
Liquid supply and vapor outlet connections
UQDB04 self-sealing, blind-mate, dripless quick-disconnect, 4 rows × 10 DN20, 4 rows × 10
Supported server quantity
40 vertically mounted 1U servers (4 rows × 10 servers per row)
Installation type
Floor-mounted or base-mounted

Two-Phase Immersion Cooling Computing Unit

Dimensions
Supports 19-inch / 21-inch servers
Configuration
Supports 8 OAM modules
Single-card heat dissipation capacity
≥ 2,500 W at OAM dimensions
Rated flow rate
0.34 LPM/kW @ HFP-D
Operating pressure
101 ± 10 kPa @ HFP-D
Ambient temperature
Operating: 10°C to 40°C / Storage: −40°C to 60°C