SynthCool PhaseLab-2PCP-020

PhaseLab 2PCP Series Tester

SynthCool PhaseLab 2PCP provides controlled two-phase flow generation at defined vapor quality, thermal load testing, single-phase flow resistance testing, and micro thermal management testing for optical modules. It delivers stable, controllable and repeatable flow, temperature, pressure, backpressure, subcooling, and vapor quality conditions for two-phase cold plates, two-phase cooling loops, optical module thermal management components, and other liquid cooling components.

Application scenariosDesigned for the development, validation, and calibration of two-phase cold plates across a wide range of power levels.

Precise Two-Phase Test Control

Integrates fluid supply, pressure control, flow distribution, heat input, and backpressure management to control coolant temperature, subcooling, inlet phase, and condensation conditions.

Wide Flow-Rate Range

Supports stable, precise flow delivery at very low flow rates. Multi-range flow meters, valves, and modular piping adapt test loops to different heat loads, flow rates, and pipe sizes.

Multi-Refrigerant Support

Supports refrigerant draining, charging, and switching for two-phase cold plate testing under different refrigerants and operating conditions.

Automated Testing and Data Tracking

Supports multi-condition test scripts, remote PID tuning, real-time data acquisition, historical data traceability, and cloud synchronization.

Technical specifications

Specifications

Model
PhaseLab-2PCP-020
Maximum heat exchange
20 kW
Secondary-side refrigerant
Primarily designed for R1233zd(E); also supports switching and adaptation to other low-GWP refrigerants such as R245fa, R1336mzz(Z), and R515B.
Primary-side refrigerant
Softened water / PG25 / EG30
Inlet temperature
15–35°C
Full-load power consumption
30 kW
Power input
3ph-380Vac 50Hz
Recommended maintenance clearance
≥ 1200 mm front and rear

For detailed technical specifications and customization options, please contact our technical team.

Back to products